02/06 505,021M
*2P0206* *P505021M*
E2006 Lennox Industries Inc.
Dallas, Texas, USA
Humiditrol
®
EDA Series Unit
The Dave Lennox Signature
t
Collection Humiditrol
®
En-
hanced Dehumidification Accessory (EDA) is designed for
installation with a Lennox R−410A split−system outdoor unit
and an air handler or a furnace with a variable speed blow-
er. This accessory is designed for indoor installations in ei-
ther upflow or horizontal air discharge applications. This
unit is for use only on R−410A systems with thermal
expansion valves.
Prior to installation, study the decision tree on page
16 to confirm that all application requirements for
EDA installation are met.
NOTE − For downflow application, refer to Installation In-
struction Supplement, Installing EDA Unit in Downflow
Configuration 505,134M.
Shipping & Packing List
S 1 − Assembled EDA indoor unit
S 1 − Bag assembly (includes check/flow restrictor for
use on EDA coil, EDA notification label).
S 1 Outdoor fan relay and wiring harness (used only
with outdoor units equipped with variable speed fan
motors)
Check the components for shipping damage. If any dam-
age is found, immediately contact the last carrier.
Other Required Components
Separately-ordered components are restricted to those
listed in the Engineering Handbook and the price book:
S SignatureStat
t
thermostat [Outdoor Sensor (46M98)
included],
− Single-stage (81M26)
− Multi−stage (81M27)
− Multi−stage heat-pump (81M28)
S Twisted Pair Wire (84X49) for outdoor sensor to ther-
mostat − Required for use with SignatureStatt.
S 75VA 24VAC indoor unit transformer (12P61) − Re-
quired when EDA unit is installed with a two-stage heat
pump system.
S Humiditrol
®
EDA Insulation and Piping Kit (refer to ap-
plications information in Lennox Engineering Hand-
book)
INSTALLATION/
SERVICE
INSTRUCTIONS
Humiditrol
®
Enhanced Dehumidification
Accessory (EDA) Units
ACCESSORIES
505,021M
02/06
Supersedes 01/06
RETAIN THESE INSTRUCTIONS
FOR FUTURE REFERENCE
Table of Contents
EDA Series Unit 1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Shipping & Packing List 1. . . . . . . . . . . . . . . . . . . . . . . .
Other Required Components 1. . . . . . . . . . . . . . . . . . . .
General Information 1. . . . . . . . . . . . . . . . . . . . . . . . . . .
Unit Dimensions 2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Installation Dimensions and Arrangement 3. . . . . . . . .
Component Functions 4. . . . . . . . . . . . . . . . . . . . . . . . . .
General Installation Information 5. . . . . . . . . . . . . . . . .
Electrical Wiring 5. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
EDA Installation Flow Chart & Procedures 5. . . . . . . .
Leak Testing, Evacuation, Charging 8. . . . . . . . . . . . . .
Insulating and Sealing the Unit 9. . . . . . . . . . . . . . . . . .
Other System Components 9. . . . . . . . . . . . . . . . . . . . .
How the EDA Unit Works 10. . . . . . . . . . . . . . . . . . . . . . .
Cooling Mode with Dehumidification ON 10. . . . . . . . . .
Cooling Mode (Dehumidification OFF) 11. . . . . . . . . . . .
Heating Mode (Heat Pump Applications) 11. . . . . . . . . .
Air Resistance Table 13. . . . . . . . . . . . . . . . . . . . . . . . . . .
Repair Parts List 13. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Wiring Diagrams 13. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Decision Tree 16. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
General Information
NOTEThese instructions are intended as a general guide
and do not supersede local codes in any way. Consult au-
thorities having jurisdiction before installation.
The Humiditrol
®
EDA unit will operate to dehumidify, as re-
quired, when ambient temperatures are below 95ºF. When
temperatures reach 95ºF, the cooling and dehumidification
requirements will both be satisfied by the increased sys-
tem runtime. In applications that include a Humiditrol
®
EDA unit, a call to activate the dehumidification mode at or
above 95ºF is unnecessary and would not be issued or al-
lowed by the SignatureStatt room thermostat.
Prior to system checkout, consider the outdoor ambient
temperature. REMEMBER, the EDA unit does NOT
function in temperatures at or above 95ºF. Plan testing
to be conducted when temperatures are between 65ºF and
95ºF to ensure proper EDA set up and checkout operation.
IMPORTANT
The approved application for the EDA Series unit is
restricted to those listed in the Engineering Hand-
book and price book.
Litho U.S.A.
Vue de la page 0
1 2 3 4 5 6 ... 15 16

Résumé du contenu

Page 1 - INSTRUCTIONS

02/06 505,021M*2P0206* *P505021M*E2006 Lennox Industries Inc.Dallas, Texas, USAHumiditrol® EDA Series UnitThe Dave Lennox Signaturet Collection Humidi

Page 2 - IMPORTANT

Page 10EDA 01/06EDA Unit OperationThe EDA coil is added to an HVAC system downstream ofthe indoor coil. In dehumidification mode, the coil becomesan e

Page 3 - AIR FLOW

Page 11EDA INSTALLATION/ SERVICE INSTRUCTIONSCooling Mode (Dehumidification OFF)Figure 10 illustrates refrigerant flow in cooling mode (dehu-midifica

Page 4 - Component Functions

Page 12EDA 01/06Check Listn Checkpoint What to Check ActionThermostat andSensorWiring Confirm Sensor connected to SignatureStatt using twisted pairwir

Page 5 - Electrical Wiring

Page 13EDA INSTALLATION/ SERVICE INSTRUCTIONSAir ResistanceTable 2 shows air volume and total air resistance for theavailable EDA models.Table 2Air R

Page 6 - Figure 4

Page 14EDA 01/06Figure 12Typical EDA/Condensing Unit Wiring DiagramINDOORUNITB4FANBlueYellowBlackK11st, cut yellowwire here.Use Wirenuts*OUTDOOR RELAY

Page 7 - 2 ft. max

Page 15EDA INSTALLATION/ SERVICE INSTRUCTIONSTypical EDA/Heat Pump Wiring DiagramFigure 13B4FANBlueYellowBlackK11st, cutyellow wirehere.Use Wirenuts*

Page 8

Page 16EDA 01/06Upflow/horizontalNOTE − AIR HANDLER REQUIRESFIELD−FABRICATED TRANSITIONBETWEEN BLOWER OUTLETAND EDA COIL.[If furnace] Select indoorcoi

Page 9

Page 2EDA 01/06WARNINGThis cased product contains fiberglass wool. Dis-turbing the insulation during installation, mainte-nance, or repair will expose

Page 10 - EDA Unit Operation

Page 3EDA INSTALLATION/ SERVICE INSTRUCTIONSInstallation Dimensions and ArrangementFigure 1AIR FLOWAIR FLOWUP-FLOW FURNACEUP-FLOW AIRHANDLEREDA−024B:

Page 11 - Figure 11

Page 4EDA 01/06Component FunctionsCharge CompensatorThe charge compensator(shown in figure 5) serves to maintain the proper amount ofrefrigerant circ

Page 12 - Check List

Page 5EDA INSTALLATION/ SERVICE INSTRUCTIONSGeneral Installation InformationWARNINGImproper installation, adjustment, alteration, ser-vice or mainten

Page 13 - Wiring Diagrams

Page 6EDA 01/06Required Parts (all applications)EDA Unit, with check/flow restrictor & labelAppropriate SignatureStatt Thermostat46M98 − Outdoor S

Page 14 - Control Wiring

Page 7EDA INSTALLATION/ SERVICE INSTRUCTIONSINDOORUNITOUTDOORUNITair−flowVaporLineLiquidLineLiquid Line fromOutdoor UnitLiquid Line toIndoor TXVTXVVa

Page 15 - Figure 13

Page 8EDA 01/06Leak Testing, Evacuating, ChargingIMPORTANTThe 3−way diverting valve actuator shaft setscrew(see figure 7) is factory set and is not to

Page 16 - Decision Tree

Page 9EDA INSTALLATION/ SERVICE INSTRUCTIONSInsulating and Sealing the UnitIMPORTANTAll piping, metering devices, and connections mustbe insulated to