02/06 505,021M*2P0206* *P505021M*E2006 Lennox Industries Inc.Dallas, Texas, USAHumiditrol® EDA Series UnitThe Dave Lennox Signaturet Collection Humidi
Page 10EDA 01/06EDA Unit OperationThe EDA coil is added to an HVAC system downstream ofthe indoor coil. In dehumidification mode, the coil becomesan e
Page 11EDA INSTALLATION/ SERVICE INSTRUCTIONSCooling Mode (Dehumidification OFF)Figure 10 illustrates refrigerant flow in cooling mode (dehu-midifica
Page 12EDA 01/06Check Listn Checkpoint What to Check ActionThermostat andSensorWiring Confirm Sensor connected to SignatureStatt using twisted pairwir
Page 13EDA INSTALLATION/ SERVICE INSTRUCTIONSAir ResistanceTable 2 shows air volume and total air resistance for theavailable EDA models.Table 2Air R
Page 14EDA 01/06Figure 12Typical EDA/Condensing Unit Wiring DiagramINDOORUNITB4FANBlueYellowBlackK11st, cut yellowwire here.Use Wirenuts*OUTDOOR RELAY
Page 15EDA INSTALLATION/ SERVICE INSTRUCTIONSTypical EDA/Heat Pump Wiring DiagramFigure 13B4FANBlueYellowBlackK11st, cutyellow wirehere.Use Wirenuts*
Page 16EDA 01/06Upflow/horizontalNOTE − AIR HANDLER REQUIRESFIELD−FABRICATED TRANSITIONBETWEEN BLOWER OUTLETAND EDA COIL.[If furnace] Select indoorcoi
Page 2EDA 01/06WARNINGThis cased product contains fiberglass wool. Dis-turbing the insulation during installation, mainte-nance, or repair will expose
Page 3EDA INSTALLATION/ SERVICE INSTRUCTIONSInstallation Dimensions and ArrangementFigure 1AIR FLOWAIR FLOWUP-FLOW FURNACEUP-FLOW AIRHANDLEREDA−024B:
Page 4EDA 01/06Component FunctionsCharge CompensatorThe charge compensator(shown in figure 5) serves to maintain the proper amount ofrefrigerant circ
Page 5EDA INSTALLATION/ SERVICE INSTRUCTIONSGeneral Installation InformationWARNINGImproper installation, adjustment, alteration, ser-vice or mainten
Page 6EDA 01/06Required Parts (all applications)EDA Unit, with check/flow restrictor & labelAppropriate SignatureStatt Thermostat46M98 − Outdoor S
Page 7EDA INSTALLATION/ SERVICE INSTRUCTIONSINDOORUNITOUTDOORUNITair−flowVaporLineLiquidLineLiquid Line fromOutdoor UnitLiquid Line toIndoor TXVTXVVa
Page 8EDA 01/06Leak Testing, Evacuating, ChargingIMPORTANTThe 3−way diverting valve actuator shaft setscrew(see figure 7) is factory set and is not to
Page 9EDA INSTALLATION/ SERVICE INSTRUCTIONSInsulating and Sealing the UnitIMPORTANTAll piping, metering devices, and connections mustbe insulated to